- Home
- Line post insulators
Line post insulators
At WINWIN Speciality Insulators (WSI), we take pride in our meticulous adherence to ANSI standards when manufacturing Line Post Insulators.
These insulators are crucial components in electrical distribution systems, and our commitment to quality ensures their reliability and performance. Line post insulators provide electrical insulation and mechanical support to the conductors, helping maintain the integrity and reliability of the electrical grid.
Our Diverse Applications
WSI offers a range of Line Post Insulators that serve a number of critical applications including:
-
VOLTAGE RANGE 11 KV TO 33 KV DISTRIBUTION LINES:
WS comprehensive range of Line Post Insulators covers the voltage range from 11 kV to 33 kV, making them suitable for a wide spectrum of distribution line applications. We can also offer insulator for rating above 33 kV based on customer requirement. Whether you're managing lower or higher voltage systems, we have the right solution to meet your needs.
-
EXPERIENCE THE WS ADVANTAGE:
At WS, we don't just meet industry standards; we set them. Our commitment to quality, precision manufacturing, and customer satisfaction makes us the preferred choice for Line Post Insulators. Trust in WS products to ensure the integrity and performance of your distribution systems. Contact us today to discuss how WS Line Post Insulators can meet your specific needs and elevate the performance of your electrical infrastructure.
Types of Line Post Insulators
Vertical Tie Top with Base and Spindle
Vertical Clamp Top with Base and Spindle
Horizontal Clamp Top with Base and Spindle
Horizontal Clamp Top with Gain Base
Custom Solutions
WSI Line Post Insulators Range
-
LINE POST INSULATORS ANSI 57-1, 57-2 & 57-3
-
LINE POST INSULATORS ANSI 57-4, 57-4 & 57-6
-
LINE POST INSULATORS ANSI 57-16 & 57-26
![](https://wsil.net/wp-content/uploads/2023/10/SKETCH-FOR-LINE-POST-57-1-TO-57-3-TABLE-1.png)
ANSI Reference Number | Units | 57-1 | 57-2 | 57-3 |
---|---|---|---|---|
Rated Voltage | kV | 11 | 22 | 22 |
Cantilever Strength (upright) | lbs (kN) | 2800 (12.5) | 2800 (12.5) | 2800 (12.5) |
Mounting Arrangement | - | Vertical | Vertical | Vertical |
Top Fixing Arrangement | - | Tie Top | Tie Top | Tie Top |
Total Height (H) | mm | 229 | 305 | 381 |
Max. Diameter of Insulating Part (D) | mm | 140 | 152 | 165 |
Spindle Size | - | 3/4'' BSW | 3/4'' BSW | 3/4'' BSW |
Total Creepage Distance | mm | 356 | 559 | 737 |
Dry Power Frequency Flashover Voltage | kV | 70 | 100 | 125 |
Wet Power Frequency Flashover Voltage | kV | 50 | 70 | 95 |
Impulse Flashover Voltage Positive | kVp | 120 | 160 | 200 |
Impulse Flashover Voltage Negative | kVp | 120 | 160 | 200 |
RIV Test Voltage | kV | 15 | 22 | 30 |
Maximum RIV | µV | 100 | 100 | 200 |
![](https://wsil.net/wp-content/uploads/2023/10/SKETCH-FOR-LINE-POST-57-4-TO-57-6-TABLE-2.png)
ANSI Reference Number | Units | 57-4 | 57-5 | 57-6 |
---|---|---|---|---|
Rated Voltage | kV | 22 | 33 | 33 |
Cantilever Strength (upright) | lbs (kN) | 2800 (12.5) | 2800 (12.5) | 2800 (12.5) |
Mounting Arrangement | - | Vertical | Vertical | Vertical |
Top Fixing Arrangement | - | Tie Top | Tie Top | Tie Top |
Total Height (H) | mm | 432 | 508 | 597 |
Max. Diameter of Insulating Part (D) | mm | 178 | 191 | 203 |
Spindle Size | - | 3/4'' BSW | 3/4'' BSW | 7/8" BSW |
Total Creepage Distance | mm | 1016 | 1143 | 1346 |
Dry Power Frequency Flashover Voltage | kV | 140 | 160 | 180 |
Wet Power Frequency Flashover Voltage | kV | 110 | 130 | 150 |
Impulse Flashover Voltage Positive | kVp | 230 | 265 | 300 |
Impulse Flashover Voltage Negative | kVp | 230 | 265 | 300 |
RIV Test Voltage | kV | 44 | 44 | 44 |
Maximum RIV | µV | 200 | 200 | 200 |
![KETCH A FOR LINE POST 57-16 TO 57-26 - TABLE 3](https://wsil.net/wp-content/uploads/2023/10/KETCH-A-FOR-LINE-POST-57-16-TO-57-26-TABLE-3.png)
![KETCH B FOR LINE POST 57-16 TO 57-26 - TABLE 3](https://wsil.net/wp-content/uploads/2023/10/KETCH-B-FOR-LINE-POST-57-16-TO-57-26-TABLE-3.png)
ANSI Reference Number | Units | 57-16 | 57-26 |
---|---|---|---|
Rated Voltage | kV | 33 | 33 |
Cantilever Strength (upright) | lbs (kN) | 2800 (12.5) | 2800 (12.5) |
Mounting Arrangement | - | Vertical | Horizontal |
Top Fixing Arrangement | - | Clamp Top | Clamp Top |
Total Height (H) | mm | 622 | 635 |
Max. Diameter of Insulating Part (D) | mm | 203 | 203 |
Spindle Size | - | 7/8" BSW | 7/8" BSW |
Total Creepage Distance | mm | 1346 | 1346 |
Dry Power Frequency Flashover Voltage | kV | 180 | 180 |
Wet Power Frequency Flashover Voltage | kV | 150 | 150 |
Impulse Flashover Voltage Positive | kVp | 300 | 300 |
Impulse Flashover Voltage Negative | kVp | 300 | 300 |
RIV Test Voltage | kV | 44 | 44 |
Maximum RIV | µV | 200 | 200 |